SATURABLE
REACTORS
In our research into different types of ballast to control
current demand on various projects, we found that it is often useful to be able
to vary the current independently of the voltage if a single power supply is to
be used for multiple projects with different V and I requirements. In the
process we ran across the concept of the Saturable Reactor. The idea is simple. Introduction of a small variable DC voltage
into a separate winding on an iron frame inductor will bring the core to
saturation, opposing the inductance of the power winding. The closer to saturation the core becomes,
the lower the inductance of the reactor and the larger the current that is
allowed to flow.
We find this concept intriguing because it offers variable
control of large currents by way of a low power control circuit. Large multi-tap autotransformers in series
with a circuit may be used to perform the function of variable current control
but their use is mechanically complicated by the necessity of multiple
connections to one or more tap switches along with the fact that the switches
cannot be operated under high current loads that exceed their
specifications. With the saturable
reactor, a simple Variac and bridge rectifier are all that should be needed to
provide infinitely adjustable current control even under load.
The simplest version of the concept – a single control winding
on the frame of a single winding inductor – is not very effective due the
transformer effect. An AC current will
be induced in the control winding that will oppose the DC introduced. This not only hampers the saturation of the
frame, but can also destroy the rectifier circuit (we found this out first
hand). After speaking with several knowledgeable
sources on the subject, the design requirements became clear. There must be 3 windings. Either the power winding or the control
winding must consist of 2 separate coils placed in series in such a manner that
no AC voltage is induced into the DC control.
To test the theory, a pilot reactor was designed. We had on hand several ‘filament
transformers’ removed from x-ray power supplies. Many of these are designed so that both the large
and small focus filament transformers are on the same ‘figure 8’ frame. Each is ‘shell wound’ with a low current
primary of fine wire underneath a higher current secondary of about #12 AWG
magnet wire in about a 10:1 reduction ratio of turns. An example is pictured below.

After removing the corner bolts that hold the leaves of the top
of the 20 lb. transformer in the next photo below, the top was carefully
removed. The transformer winding pairs
were then slid off the legs. The
secondaries, which were connected in series, were then unwound/slid
off of the primaries. The primaries were
then reinstalled on the outer legs of the transformer and the combined
secondaries were then re-wound onto the center leg. Because the center winding was much stouter,
it was chosen as the inductive/power winding, making the 2 windings on the
outer legs the control windings. These
two control windings were placed in series by connecting together one lead from
each winding (using the green and black wires shown not connected in the photo below).

The leaves of the top of the transformer frame were then
meticulously re-interleaved with those of the legs and the frame
re-bolted. The inductance of the center
winding was measured ‘live’ by placing a voltage across it and using an ammeter
in series. Inductance was calculated via
the formula: L=v/ωi and found
to be 278 mH. A voltmeter across the
combined control windings showed a very significant voltage in them when the
center winding was powered up. The
series connection was broken and the lead from one control winding was swapped
with the other of its pair and this then used to reconnect the windings in
series (green and green wires shown connected in the photo above). Powering up the center winding again resulted
in virtually no induced voltage in the control windings.
The center winding was placed in series in a circuit that is
known to draw a current of 8-9 amps without ballast. An ammeter in the circuit showed a little
over 800 milliamps flowing with the inductor in place. The full-wave rectified output of a Variac
was introduced into the series pair of control windings and the voltage
gradually increased. Over the range of
0-25 VDC control voltage, the current in the power circuit also gradually increased
proportionally to its full value of a little over 8 Amps. Power was removed from both circuits after a
few minutes of operation and the system checked for problems. No significant heat was apparent at the rectifier
or in any of the windings. This is
considered to be a successful test of the theory using 2 control windings and
one power winding.
The obvious next steps seemed to be to test the theory using 2
power windings and only a single control winding, to use a larger system with
much higher current, and even to test the use of toroidal cores in the
design. The 180 lb. 3-phase shunt
transformer pictured below was chosen to test the first two of these.

The transformer has 8 leads (taps) for each leg. The middle 6 on each leg were secured out of
the way and only the start and end leads for each leg were used. The end windings, A & C, were connected
in series in such a way that there was 0 Volts in the center winding, B, when
the A-C series was energized. Using the
A-C series as the power windings resulted in the control winding drawing a huge
amount of DC current – an arrangement that would probably work but seemed
impractical. For this reason, the
configuration was reversed and B was now the inductor and the A-C series the
control. With no DC in the control
windings, the inductance of B was so high that a 10 kVA
pole pig running almost to dead short (1/16 inch gap)
produced no visible spark!
240 VDC at 12.5 Amps was then introduced into the A-C control
winding series and the pig sprang to life, producing a Jacob’s climbing arc
with plasma about 1 cm in width. The
response was weak but it did appear that at 240 VDC we were at least on the
magnetization curve for this brute. Since it was originally designed for and used
in a 480 to 560 Volt system, it seemed that it would probably require
considerably higher voltage to saturate the huge frame. We have a large autotransformer with output
voltage to 700VAC with 240 Volts in that will be used to follow up on
this. Up to 600 VDC were introduced into
the control winding via a 160 Amp bridge rectifier. The current demand in the control winding
again was huge and required ballast. A
small hobby welder was used and quickly overheated due to the current. No significant change in inductance was
produced.

To pursue the question of how to apply this concept to toroidal
systems, we disassembled the 125 kV, 300 m.a.
Bennett T-835 x-ray high voltage generator pictured above. The HV transformers are mounted on opposite
sides of a 70lb. toroidal core. This
assembly was removed and the secondaries were cut away to leave only the
primaries intact.

The direction of the magnetic flux in a toroidal core is either
clockwise or counterclockwise, depending on the winding direction of the coil
producing it and which half-cycle of the AC is present in it. There are two ways to connect the two
primaries above in series – connecting one set of leads from the same end of
each coil or connecting the leads from opposite ends. One method will cause the magnetic fluxes
from each of the coils to oppose each other and the other will result in the
fluxes aiding each other. Inductance of
one hookup measured only 16 mH while the opposite hookup measured 2.7
Henries! Next, a third winding is added
on one of the free sides such that no voltage is developed in it when the
seriesed primaries are energized.
200 turns of #22 AWG magnet wire were wound around the core and
used for the control winding. Again, a
very large current demand was observed in the control winding which began to
overheat almost immediately. Neither the
use of a second oppositely wound control nor switching to 50 turns of #8 AWG
magnet wire resulted in controllable saturation.
The failures were unexpected, signaling the need for further
research. To this end, a second
authority was contacted. The retired
engineer who built saturable reactors for use in military equipment explained
that SR’s operate on the principle of ‘Amp-turns.’ This means for example, that if the power
winding has X number of turns and is passing 100 Amps, a control winding with
the same number of turns (such as the experiment above) would also take 100
Amps to control. Placing 100 times the
number of turns in the control winding as are in the power winding, would
reduce the current required to control the reactor to 1 Amp. The control winding should also be wound of
wire with about 0.01 of the cross-sectional area as the wire used in the power
winding.
Although this did explain why the first experiment above worked
so well and the other two failed, significant design drawbacks were immediately
apparent. The winding of 15,000 turns to
control an inductor of 150 turns was daunting to say the least. Also, the 1:100 turns ratio could easily
result in a dangerous high voltage transformer if a mistake in design resulted
in the primary fluxes not being cancelled out.
Consideration of this dilemma brought to mind an interesting
possibility. X-ray transformers typically
produce voltage step up on the order of 1:500.
There are often dual 1:250 transformers used that are out of phase with
each other to produce the 1:500 step up. The secondaries thereof are often dual
windings each of which are in around 1:100 or so winding ratio with respect to
their primaries. The ratio of cross
sectional area of the wire used in the primaries versus the secondaries is
certainly at least 100X. It seems we may
have been a bit hasty in having secondaries cut off of the Bennett transformer
pictured above. Fortunately, we have a
supply of these transformers with which to experiment. Using an identical Bennett T-835 unit, we
began a more detailed experimental analysis of the transformation and
inductance properties of the windings as follows:

1.
Secondaries connected in series for the control winding and the
outputs connected to HV side of NST the low side of which is connected to a DMM
2.
Primaries connected in series for the power winding
3.
10-40 volts applied to primary while monitoring the DMM. A reading of 0 VAC reflects successful wiring
scheme. 25-100VAC indicates HV output
and requiring one lead in the series connection of the primaries to be
reversed.
4.
Series ammeter testing is done on primary with secondaries open
to determine baseline inductance.
5.
DC output of a Variac is then cautiously applied across the
control winding and the voltage range required to increase the current reading
on the ammeter is noted.
6.
Place the secondaries in series opposing and test again
7.
Place the secondaries in parallel and test again
8.
Place the secondaries in anti-parallel and test again
|
PRIMARIES |
SECONDARIES |
INPUT |
OUTPUT |
AT 250 VAC |
|
S-OPPOSE |
S-AIDING |
25 |
184 |
1840 |
|
S-OPPOSE |
S-OPPOSE |
25 |
2163 |
21630 |
|
S-OPPOSE |
PARALLEL |
25 |
1375 |
13750 |
|
S-OPPOSE |
ANTI-PARALLEL |
25 |
388 |
3880 |
|
S-AIDING |
S-AIDING |
25 |
2375 |
23750 |
|
S-AIDING |
S-OPPOSE |
25 |
1688 |
16880 |
|
S-AIDING |
PARALLEL |
25 |
193 |
1930 |
|
S-AIDING |
ANTI-PARALLEL |
25 |
1500 |
15000 |
Secondaries have the 4 possible connection configurations shown
below. The dots represent connections to
the Federal HV receptacles.
SERIES PARALLEL
For the sake of completeness and to determine where we are on
the magnetization curve when using 25 VAC as the test voltage, the other 8
possible configurations of the windings were tested:
|
PRIMARIES |
SECONDARIES |
INPUT |
OUTPUT |
AT 250 VAC |
|
PARALLEL |
S-AIDING |
25 |
0 |
0 |
|
PARALLEL |
S-OPPOSE |
25 |
13 |
1625 |
|
PARALLEL |
PARALLEL |
25 |
19 |
2375 |
|
PARALLEL |
ANTI-PARALLEL |
25 |
0.5 |
62.5 |
|
ANTI-PARALLEL |
S-AIDING |
25 |
20 |
2500 |
|
ANTI-PARALLEL |
S-OPPOSE |
25 |
0 |
0 |
|
ANTI-PARALLEL |
PARALLEL |
25 |
0 |
0 |
|
ANTI-PARALLEL |
ANTI-PARALLEL |
25 |
20 |
2500 |
* Indicates a huge current draw that tripped the 15 Amp breaker even at 25 VAC input even though no output voltage
registered.
We have also found that it is possible to use 2 transformers to
create an SR. MOT’s seemed ideal with turns ratios around 20:1.
We were able to find 2 identical heavy duty units built by Advance and 2
others by YEC:

For each pair, the primaries were wired together in
parallel. The secondaries were placed in series by connecting the HV tab
of each unit and connecting a wire to the frame of each by means of a bolt run
through one of the mounting hotels in the frame. These output wires were
connected to the HV side of a 125:1 NST to which a DMM was connected to the
Direct measurement of the inductance of the paralleled primaries
was then performed with an ammeter in series with the input supply circuit set
at 35 VAC. The ammeter registered about ½ Amp, indicating a baseline
inductive reactance of around 60 Ohms. The ends of the seriesed secondary
circuit were the wires attached to the frame of each transformer. This
series forms the DC control winding. These wires were attached to the rectified
output of a small Variac. The introduction of 0-82 VDC into the control
caused the reading on the ammeter to increase smoothly over the range to a
final value of 16.9 Amps. We did not push this further due to the 20 Amp
limitation of the ammeter, but this corresponds to an inductive reactance of
slightly over 2 Ohms, making the test a resounding success. With cooling,
this pair could reasonably be expected to handle 40 or 50 Amps as ballast and
the other pair gave a very similar test result.
The question then became whether the two pairs could be successfully
paralleled for higher current handling capability. To this end, shunt
wires were run to connect two sets of paralleled primaries. Then, the two
sets of seriesed secondaries were connected in parallel with respect to each
other. A brief power test was performed just to insure that no voltage
was induced into the control. At this point, the inductance/saturation
testing was repeated on the combination of all 4 MOTS. The testing
was also very successful and the results very similar to those from the tests
of the individual pairs with a couple of exceptions, which are as
follows. First, the baseline reactance was reduced to about ½ of the
value measured on the individual pairs – 30 Ohms instead of 60. This was
to be expected pursuant to the law of parallel inductors. Second and more
surprising, there was only required a total of 28 VDC in the control to reduce
this value to 2 Ohms. It would seem to follow that more pairs could be
added with a corresponding increase in current capability and decrease in
baseline reactance. The high end reactance drop should not resent a
problem since the useful range of inductive reactance for most of our project
work is about 2-8 Ohms.


Another interesting project will be to use the transformers
inside of a pair pole pigs for a similar experiment:


The